CRPS Redundant

ZIPPY is capable of producing small quantities of multiple sizes and changing specifications according to customers' needs, so as to meet customers' demands at any time.

ZRL2-5BF1K2V

FEATURES
  • 80 PLUS PLATINUM
  • 1+1 Redundant Application
  • Support PMBus 1.2
  • Fan Reverse Option
  • Smart Fan Speed Control
  • Protections:OVP/OCP/SCP/UVP/OTP/Fan Lock
  • Operation Altitude:5000meters
Dimension
325(D)*76(W)*84(H)
Application (Form Factor)
  • CRPS Redundant
  • 2U Redundant
INPUT CHARACTERISTICS
Parameter Notes & Conditions Min. Type. Max Units
Operating Voltage Range 90 264 Vac
Input Frequency Range 47 63 Hz
Maximum Input Current *Io=100%;Vin=90Vac
*Io=100%;Vin=180Vac
16 A
Leakage Current per module 3.5 mA
Inrush Current *Vin=115Vac,Cold start/25℃
*Vin=230Vac,Cold start/25℃
*per module
15
30
A

 

OUTPUT CHARACTERISTICS
WATTAGE OUTPUT
5V 3.3V 12V -12V 5VSB
2600W 36A 31A 215A(180-264V)
96A(90-132V)
0.5A 3.5A
Load Regulation +/-5% +/-5% +/-5% +/-10% +/-5%
Ripple & Noise 50 50 120 120 50

 

ENVIRONMENTAL SPEC.
Parameter Notes & Conditions Min. Type. Max. Units
Temperature *refer derating curve 0 70
Relative Humidity Non-condensing 20 80 %
Emissions EN55032
FCC Part15
CLASS A
Surge EN61000-4-5
DM:+/-1KV
CM:+/-2KV
Harmonic Currents EN 61000-3-2 CLASS D

 

GENERAL SPEC.
Parameter Notes & Conditions Min. Type. Max Units
MTBF Io=100%;Ta=25℃
per MIL-HDBK-217F
202507 Hours
Efficiency Io=100%;Vin=240Vac
(one power unit)
90 %
Power Density per module 54.73 W/in3
File description File name