CRPS Module

ZIPPY is capable of producing small quantities of multiple sizes and changing specifications according to customers' needs, so as to meet customers' demands at any time.

ZRH-2BG0K2

FEATURES
  • 80 PLUS PLATINUM
  • N+1 Redundant Application
  • Support PMBus 1.2
  • Fan Reverse Option
  • Smart Fan Speed Control
  • Protections OVP/OCP/SCP/UVP/OTP/Fan Lock
  • Dual Input Voltage Application
Dimension
185(D)*73.5(W)*40(H)
Application (Form Factor)
  • CRPS Module
  • 1U Redundant Module
INPUT CHARACTERISTICS
Parameter Notes & Conditions Min. Type. Max Units
Operating Voltage Range Dual Input 90
180
264
310
Vac
Vdc
Input Frequency Range AC Input 47 63 Hz
Maximum Input Current *Io=100%;Vin=90Vac
*Io=100%;Vin=180Vac
16 A
Leakage Current Acin Only 3.5 mA
Inrush Current 35 A

 

OUTPUT CHARACTERISTICS
WATTAGE OUTPUT
12V 12VSB
2700W
ACin:225A(230-264V)
      208A(180-230V)
      116.7A(115-127V)
      100A(90-115V)

DCin:225A(230-310Vdc)
      208A(180-230Vdc)
4A
Load Regulation +/-5% +/-5%
Ripple & Noise 180 120

ENVIRONMENTAL SPEC.
Parameter Notes & Conditions Min. Type. Max. Units
Temperature *refer derating curve 0 60
Relative Humidity Non-condensing 10 85 %
Emissions EN55032
FCC Part15
CLASS A
Surge EN61000-4-5
DM:+/-1KV
CM:+/-2KV
Harmonic Currents EN 61000-3-2 CLASS D

 

GENERAL SPEC.
Parameter Notes & Conditions Min. Type. Max Units
MTBF Io=100%;Ta=25℃
per MIL-HDBK-217F
133095 Hours
Efficiency Io=50%;Vin=230Vac 94 %
Power Density 81.41 W/in3