CRPS Redundant

ZIPPY可依客戶需求進行少量多樣化生產及規格化的變更,隨時滿足客人需求。

DZRH2-5AB0V2V

FEATURES
  • 1+1 Redundant Application
  • Support PMBus 1.2
  • Fan Reverse Option
  • Smart Fan Speed Control
  • Protections:OVP/OCP/SCP/UVP/OTP/Fan Lock
  • Operation Altitude:5000meters
Dimension
245(D)*76(W)*84(H)
Application (Form Factor)
  • CRPS Redundant
  • 2U Redundant
INPUT CHARACTERISTICS
Parameter Notes & Conditions Min. Type. Max Units
Operating Voltage Range -36 -72 Vdc
Input Frequency Range
Maximum Input Current *Io=100%;Vin=-36Vdc
*Io=100%;Vin=-54Vdc
39
27.5
A
Leakage Current
Inrush Current *per module 25 A

 

OUTPUT CHARACTERISTICS
WATTAGE OUTPUT
5V 3.3V 12V -12V 5VSB
1200W 20A 20A
100A(-42--72V)
83.3A(-36--42V)
0.5A 3.5A
Load Regulation +/-5% +/-5% +/-5% +/-10% +/-5%
Ripple & Noise 50 50 120 120 50

 

ENVIRONMENTAL SPEC.
Parameter Notes & Conditions Min. Type. Max. Units
Temperature 0 50
Relative Humidity Non-condensing 10 85 %
Emissions EN55032
FCC Part15
CLASS A
Surge EN61000-4-5
DM:+/-1KV
CM:+/-2KV
Harmonic Currents

 

GENERAL SPEC.
Parameter Notes & Conditions Min. Type. Max Units
MTBF Io=100%;Ta=25℃
per MIL-HDBK-217F
192974 Hours
Efficiency Io=50%;Vin=-48V
(one power unit)
87 %
Power Density per module 36.18 W/in3